FBT系列闭式冷却塔配套选型表
|
序号
|
高频电源
|
中频电源
|
中频淬火 成套设备
|
中频 透热炉
|
中频感应 保温炉+电源
|
中频感应 熔炼炉+电源
|
密封式冷却塔 预选型号
|
|
1
|
30KW
|
KGPS1/250
|
60KW
|
GTJ8-60-1-8
|
|
GWJ0.05-60/1
|
FBT-1
|
|
2
|
60KW
|
KGPS1/350
|
125KW
|
GTJ8-100-1-8
|
|
GWJ0.15-100/1
|
FBT-2
|
|
3
|
100KW
|
KGPS1/600
|
200KW
|
GTJ8-160-1-8
|
GWBJ0.5-160/1
|
GWJ0.25-160/1
|
FBT-3
|
|
4
|
200KW
|
KGPS1/1000
|
250KW
|
GTJ8-250-1-8
|
GWBJ1.0-250/1
|
GWJ0.5-250/1
|
FBT-4
|
|
5
|
300KW
|
KGPS1/1500
|
350KW
|
GTJ8-350-1-8
|
GWBJ3-350-1
|
GWJ1.0-350/1
|
FBT-5
|
|
6
|
|
KGPS1/2000
|
500KW
|
GTJ8-500-1-8
|
GWBJ5-500/1
|
GWJ1.5-500/1
|
FBT-6
|
|
7
|
400KW
|
KGPS1/3000
|
600KW
|
GTJ8-600-1-8
|
GWBJ5-600/0.5
|
GWJ1.5-600/1
|
FBT-7
|
|
8
|
|
KGPS0.3-3000
|
750KW
|
GTJ8-750-1-8
|
GWBJ7-750/0.5
|
GWJ2-800/0.5
|
FBT-9
|
|
9
|
|
KGPS0.3-4000
|
1000KW
|
GTJ8-1000-1-8
|
GWBJ10-1000/0.3
|
GWJ2-1000/0.5
|
FBT-10
|
|
10
|
800KW
|
KGPS0.3-5000
|
|
GTJ8-1250-1-8
|
GWBJ12-1250/0.5
|
GWJ2-1250/0.5
|
FBT-13
|
|
11
|
1200KW
|
KGPS0.2-6000
|
|
GTJ12-1500/0.3
|
GWBJ15-1500/0.3
|
GWJ5-1500/0.3
|
FBT-16
|
|
12
|
|
|
|
GTJ12-2000/0.5
|
|
GWJ6-2000/0.3
|
FBT-19
|
|
13
|
|
|
|
GTJ12-2500/0.5
|
GWBJ25-2000/0.3
|
GWJ8-2500/0.3
|
FBT-21
|
|
14
|
|
|
|
GTJ12-3000/0.5
|
|
GWJ10-3000/0.3
|
FBT-22
|
|
15
|
|
|
|
|
|
GWJ10-3500/0.3
|
FBT-24
|
|
16
|
|
|
|
|
|
GWJ10-4000/0.3
|
FBT-27
|
选型方法 首先求得设备满负荷运行产生的热量Qs(kcal/h),根据冷却塔的技术参数,然后找到相对的冷却塔的冷却能力Q(kcal/h)。 正确的选型要尽可能多的掌握使设备产生热量的相关的数据,例如设备产生热量所做的无效功率,循环水流量,正常的温升范围,当地的环境湿球温度等。 在常见的环境条件下,我们可以用以下的简便方法计算设备运行产生的热量,作为选型的基本依据: 1:Qs=流量(L/h)×流体比热×温升 2:Qs=设备运行的无效功率×860(换热系数) 3:Qs=淬火工件产量(kg/h)×工作的热容 4:Qs=理算数据+实际使用的经验值 注:在不同的地区,不同的环境条件下,冷却塔的散热量与当地环境湿球温度关系很大,冷却塔在设计排风量和喷淋水量方面有相应的变化,恕不另行告之。
|